Flow induced corrosion/erosion of 6061-T6 aluminum in de-ionized (DI) water environments has not been studied widely. Especially, the long-term effects of corrosion/erosion in seemingly benign flow velocity, temperature, and resistivity ranges of 8 ft/s, 85 oF, 3-5 MOhm-cm, respectively. This study concludes that the flow induced corrosion/erosion in the above parameter ranges is minimal. This is detailed by presenting a literature survey, measuring pipe wall samples from a system that has operated in the above parameter range, predict the loss of material in mm/year at the above velocities and at higher temperatures using electric potential values from other experimental studies coupled with wall shear stress simulated using Computational Fluid Dynamic (CFD) analysis.